The `knx` climate platform is used as in interface with KNX thermostats.
|
||||
|
||||
KNX thermostats use at least 2 group addresses: one for the current temperature and one for the target temperature (named set-point in KNX terms).
|
||||
The `knx` component must be configured correctly, see [KNX Component](/components/knx).
|
||||
|
||||
To use your KNX thermostats in your installation, add the following to your `configuration.yaml` file:
|
||||
To use your KNX thermostats in your installation, add the following lines to your `configuration.yaml` file:
|
||||
|
||||
```yaml
|
||||
# Example configuration.yaml entry
|
||||
climate:
|
||||
- platform: knx
|
||||
address : KNX_ADDRESS
|
||||
temperature_address: 0/1/1
|
||||
setpoint_address: 0/1/0
|
||||
- platform: knx
|
||||
name: HASS-Kitchen.Temperature
|
||||
temperature_address: '6/2/1'
|
||||
setpoint_address: '5/1/2'
|
||||
target_temperature_address: '5/1/1'
|
||||
operation_mode_address: '5/1/3'
|
||||
```
|
||||
|
||||
- **address** (*Required*): The KNX group address that is used to turn on/off this actuator channel.
|
||||
- **temperature_address** (*Required*): The group address that is used to communicate the current temperature. Data format must be datapoint type 9.001 DPT_Value_Temp (2-Octet float value), check [details](http://www.knx.org/fileadmin/template/documents/downloads_support_menu/KNX_tutor_seminar_page/Advanced_documentation/05_Interworking_E1209.pdf).
|
||||
- **setpoint_address** (*Required*): The group address that is used to set/read the target temperature. Data format must be datapoint type 9.001 DPT_Value_Temp (2-Octet float value). Make sure, you set the read-flag for the thermostat to allow Home Assistant to read the target temperature.
|
||||
- **name** (*Optional*): A name for this devices used within Home Assistant.
|
||||
Alternatively, if your device has dedicated binary group addresses for frost/night/comfort mode:
|
||||
|
||||
```yaml
|
||||
climate:
|
||||
- platform: knx
|
||||
name: HASS-Kitchen.Temperature
|
||||
temperature_address: '6/2/1'
|
||||
setpoint_address: '5/1/2'
|
||||
target_temperature_address: '5/1/1'
|
||||
operation_mode_frost_protection_address: '5/1/3'
|
||||
operation_mode_night_address: '5/1/4'
|
||||
operation_mode_comfort_address: '5/1/5'
|
||||
```
|
||||
|
||||
|
||||
* **name** (*Optional*): A name for this device used within Home Assistant.
|
||||
* **temperature_address**: KNX group address for reading current room temperature from KNX bus.
|
||||
* **target_temperature_address**: KNX group address for reading current target temperature from KNX bus.
|
||||
* **setpoint_address**: KNX group address for basis setpoint
|
||||
|
||||
* **operation_mode_address** (*Optional*) KNX address for operation mode (Frost protection/night/comfort).
|
||||
* **operation_mode_state_address** (*Optional*) Explicit KNX address for reading operation mode
|
||||
* **controller_status_address** (*Optional*) KNX address for HVAC controller status (in accordance with KNX AN 097/07 rev 3)
|
||||
* **controller_status_state_address** (*Optional*) Explicit KNX address for reading HVAC controller status
|
||||
|
||||
* **operation_mode_frost_protection_address** (*Optional*) KNX address for switching on/off frost/heat protection mode.
|
||||
* **operation_mode_night_address** (*Optional*) KNX address for switching on/off night nmode.
|
||||
* **operation_mode_comfort_address** (*Optional*) KNX address for switching on/off comfort mode.
|
||||
|
||||
`operation_mode_frost_protection_address` / `operation_mode_night_address` / `operation_mode_comfort_address` are not necessary if `operation_mode_address` was specified.
|
||||
|
||||
|
||||